Server room cooling in Ilford
Servers turn almost every watt they draw into heat, and a closed cupboard has nowhere to put it. In Ilford we fit dedicated cooling for server rooms, comms cupboards and single racks, sized from the equipment's power draw and run on its own controller, day and night, all year.
Protect the rack
Leave three details and we phone you to talk it through.
- Sized from the kit's power draw
- Separate from the office thermostat
- Runs nights and weekends
How warm can a server room safely get?
Between 18 and 27°C, and ideally no warmer than 25°C, according to Server Room Environments, which also suggests relative humidity of 45% to 50%. Where a UPS with VRLA batteries shares the space, it suggests 20 to 25°C for their sake. Your equipment makers' own limits come first where they are tighter. A cupboard that climbs past 27°C every summer afternoon is outside all of those ranges. Source: Server Room Environments.
How is the cooling load for a rack worked out?
Mostly from the power the equipment draws, because that power becomes heat: Server Room Environments' example is a 900W server giving out 900W. To that total of servers, switches, storage and UPS losses, its method adds lighting, an allowance of 400 BTU for each person working in the room, any sun through a window, and a safety factor for future expansion. At 3,412 BTU an hour to the kilowatt, a rack drawing a steady 2kW needs about 6,800 BTU an hour of cooling before any margin (our sum). The guide itself calls its method a starting point, to be settled by a survey, and readings from your UPS or power strips make ours quicker. Source: Server Room Environments.
Why not rely on the building's air conditioning or a fan?
Because neither works when the rack needs it most. Office systems go off at night and at weekends, and they respond to a sensor out among the desks, not in the cupboard. A fan only moves outside air, and outside air is often too warm: summer 2026 was provisionally the warmest on record in the UK, peaking at 38.2°C at Hartpury College on 13 August, and the Met Office's long-run averages for Greenwich, about six miles away, put the typical July afternoon at 23.75°C. A dedicated unit with its own controller keeps the room in range whatever the office or the weather is doing. Sources: Met Office, summer 2026; Met Office, Greenwich averages.
What backup and alarms should a server room have?
At the very least, a high-temperature alert sent to the phone or inbox of someone who can act. Beyond that, the design follows what downtime costs you:
- a second unit on standby that takes over automatically if the first fails;
- the cooling on its own electrical circuit, so a fault elsewhere does not take it down;
- a condensate pump with an alarm, where the water cannot drain by gravity;
- a yearly service on both units, so the standby is known to work.
A small firm with one switch and a storage box needs less than a business holding client data on site.
Is the server cooling included in a TM44 inspection?
It can be. The TM44 guidance counts all the air conditioning units in one building controlled by the same person as one system, and says cooling for applications such as server rooms can be inspected. So add the server unit's output to the office units before deciding you are under the 12kW threshold; above it, inspections can be no more than five years apart. Where that leaves a business in our area is covered on the Ilford air conditioning homepage. Source: GOV.UK.
Common questions
Will the equipment have to be shut down for the installation?
Normally not. The work goes around the rack rather than into it, and anything that carries a risk is agreed with whoever looks after your IT before we start.
Our comms cupboard has no outside wall. Can it still be cooled?
Usually, by running pipework through a ceiling void or riser to an outdoor unit elsewhere. The length of the route and where the condensate can go decide it.
Is one small rack worth a dedicated unit?
Send us its power draw and the size of the room and we will say. A heavily used rack shut away in a cupboard usually needs one; a lightly loaded rack with good airflow around it may manage without.
Sources for this page
Five things to have handy
Answers to these let us judge, before anyone visits, how involved the job will be.
- Your postcode
- The building: terrace, semi, detached, a flat in a block or over a shop, or business premises
- Whether you own it outright, hold a lease or rent it
- Which room it is, its rough size, and whether it gets the morning or the afternoon sun
- Anything that limits outside changes: a conservation area, a listing, a lease clause or a managing agent
Server room cooling near Ilford
Need server room cooling just beyond Ilford? Every town below has its own page on local housing, the council and the planning points that decide where a unit can go. For Ilford itself, read air conditioning in Ilford.
Guides to read before you decide
Sizing an air conditioner: kilowatts, BTU and the room in front of you
Two published sizing tables side by side, the conversion between them, and what changes the answer.
Air conditioning costs: fitting, wiring and the bills that follow
National figures for the unit, the labour and the wiring, then the extras a lease, a landlord or a conservation area can bring.
Checking the F-gas register before you hire an air conditioning firm
The firm's certificate, the engineer's own qualification, how to check both, and where R32 sits in the leak-check rules.
Similar jobs we take on
Office air conditioning
Open-plan floors, meeting rooms and offices above shops, cooled to suit the headcount and the equipment.
Commercial air conditioning
Cooling for the shop floor, the salon chair and the kitchen pass, sized for a door that never stays shut and placed with the flats upstairs in mind.
Everything else we do
Air conditioning installation
Planned from survey to switch-on: a wall-mounted split, with the route, the wiring, the consents and the neighbours' window worked out before we drill.
Home air conditioning
For the bedroom that is still warm at midnight, the top-floor flat and the loft room: quiet indoor units that heat the same space in winter.
Air-to-air heat pumps
A reversible split chosen as a room's main heater, delivering several kilowatt-hours of warmth for every one it uses, with summer cooling included.
Multi-split air conditioning
One outdoor box running the bedrooms and the front room at once, each room set to its own temperature by its own remote.
Conservatory air conditioning
Glass rooms, garden offices and studios made usable from the summer glare to a January frost.
Air conditioning servicing
Filters, coils and drain cleaned and the system measured against its rating, on any make, with the legal leak check added only where the charge requires it.
Air conditioning repairs
No cooling, water on the floor, frosted pipes or a flashing code: the cause found first, then a price.
Rather we called you?
Your name, phone number and postcode are all we need to call you. A word about the room helps us come prepared. You can also call 020 8176 6154.